Electromagnetic Flowmeter
BTU Meter 6430
Measures Energy Flow precisely and conveniently
Introduction
BTU/Heat Meter is designed to measure the rate of thermal energy flow and total energy consumption in liquid heating and cooling applications. To know precisely the amount of energy extracted, rely on Adept BTU Meter. It measures parameters such as flow of the medium, and inlet & outlet temperatures. Net Heat Transfer is automatically calculated by using this data of temperature difference.
Salient Features
It uses the most accurate Electromagnetic/Ultrasonic Flowmeter
Matched pair of accurately calibrated Temperature Sensors
Displays instantaneous and totalised flow
Non-volatile memory stores data in case of power failure
Password protection for all programming modes
All Flowmeters are factory calibrated to ensure highest accuracy
User-defined flow units for the Flowmeters
User-defined units for Net heat Computing
Easy-to-operate keypad. Just 3 keys to select desired operating mode
Computer interface to supervisory computer through BACnet IP or RS 485 communication port
Applications
Commercial offices for tenant billing
Cooling measurement in water-based systems
Power and flow limiter with valve control
Water and waste water management
Mining industries
Residential apartments for tenant billing
Leak surveillance of hot and cold water installations
Energy measurement in open systems
Dredging industries
Salient Features
It uses the most accurate Electromagnetic/Ultrasonic Flowmeter
Matched pair of accurately calibrated Temperature Sensors
Displays instantaneous and totalised flow
Non-volatile memory stores data in case of power failure
Password protection for all programming modes
All Flowmeters are factory calibrated to ensure highest accuracy
User-defined flow units for the Flowmeters
User-defined units for Net heat Computing
Easy-to-operate keypad. Just 3 keys to select desired operating mode
Computer interface to supervisory computer through BACnet IP or RS 485 communication port
Applications
Commercial offices for tenant billing
Cooling measurement in water-based systems
Power and flow limiter with valve control
Water and waste water management
Mining industries
Fertilizers industries
Residential apartments for tenant billing
Leak surveillance of hot and cold water installations
Energy measurement in open systems
Dredging industries
Product Selection Guide
Parameters | Specifications |
---|---|
Power supply | 80 – 300 V AC |
Flowmeter input | 4 – 20 mA DC from Flowmeter (Ultrasonic/Electromagnetic/Any other) |
Temparature input | Matched Pair of PT-100 Sensors or PT 1000 sensors , Standard length – 6m |
Display | 2 Line LCD |
Communication | RS 485 (Modbus RTU), BACnet IP (Optional) |
Mounting | Wall Mount |
Accuracy | ± 0.1% of measured value |
Output – Analog | 4 – 20 mA DC |
Output – Contact | Relay (Optional) |
Energy function | Heat/Cool |
Energy display | W, J, BTU, Cal |
Sampling period | 1 sec. |
Environment temp. | Up to 65°C |
Water temp. | 0 to 50°C (Please consult factory for any other liquid.) |
Enclosure class | IP 65 |